| Elecrtical characteristics |
|
|
|
|
|
| Number of protected pairs |
|
|
1 (2 conductors) |
|
|
| Nominal operating voltage (DC) |
Un |
|
120V |
|
|
|
| Max.continuous operating voltage (DC) |
Uc |
|
170V |
|
|
| Rated load current at 25 ˚C |
IL |
|
250mA |
|
|
| Nominal discharge current (8/20μs) |
In |
|
10kA |
|
|
| Max.discharge current (8/20μs) |
Imax |
|
20kA |
|
|
| Impulse current (10/350μs) |
Iimp |
|
2.5kA |
|
|
| Residual voltage at 5kA (8/20μs) |
Ures |
<700V |
<500V |
<350V |
| Rated spark overvoltage |
(a/b-PG) |
184-276V |
184-276V |
184-260V |
|
(a-b) |
184-550V |
184-264V |
184-260V |
| Response time of overvoltage protection |
tA |
<100ns |
<25ns |
<1ns |
| Thermal protection |
|
|
YES |
|
|
| Insulation resistance of the protection |
Riso |
|
≥170MΩ |
|
|
| Serial resistance |
R |
|
approx.0.3Ω |
|
|
| Serial inductance |
L |
|
approx. 50μH |
| Inductance in the loop |
|
|
<0.5μH |
|
|
| Limit frequency (-3dB |
Zk=120Ω) |
fG |
>22MHz |
>14MHz |
>17MHz |
| Mechanical characteristics |
|
|
|
|
|
| Temperatur range |
|
|
-25˚C…+60 ˚C |
|
|
| Terminal cross section |
|
|
Stranded to 6mm² |
|
|
| Terminal screw torque |
|
|
2.0Nm |
|
|
| Degree of protection IEC/EN 60529 |
|
|
IP20 |
|
|
| Housing material |
|
|
Thermoplastic; yellow. Extinguishing degree V-0 |
|
|
| Mounting IEC/EN 60715 |
|
|
35mm DIN rail |
|
|
| Ordering information |
|
|
|
|
|
| |
|
IM-xDSL |
IM-xDSL-V |
IM-xDSL-T |
| Ordering code IM-xDSL |
|
704002 |
704006 |
704010 |
| Ordering code IM-xDSL (base 2GND) |
|
704003 |
704007 |
704011 |