| Type |
|
IM-DB 9 |
| Elecrtical characteristics |
|
|
|
| Number of preotected pairs |
|
8 |
| Nominal operating voltage (DC) |
Un |
12V |
| Max.continuous operating voltage (DC) |
Uc |
15V |
| Nominal discharge current (8/20μs) |
In (line-line) |
100A |
|
(lines-PG) |
1kA |
| Max. discharge current (8/20μs) |
Imax (line-line) |
200A |
|
(lines-PG) |
2kA |
| Protection level at In |
Up (line-line) |
≤30V |
|
(line-PG) |
≤200V |
| Protection level at 1kV/μs |
Up (line-line) |
≤24V |
|
(line-PG) |
≤30V |
| Response time of overvoltage protection |
tA |
<1ns |
| Transverse capacitance |
C (line-line) |
600pF |
|
(lines-PG) |
700pF |
| Limited frequency |
fG |
500kHz |
| Mechanical characteristics |
|
|
|
| Connection |
|
9 pole M/F |
| Termination |
|
DB 9 male – DB 9 female |
| Temperatur range |
|
-40˚C…+80˚C |
| Degree of protection IEC/EN 60529 |
|
IP20 |
| Housing material |
|
Thermoplastic; extinguishing degree UL 94 V-0 |
| Ordering information |
|
|
|
| Un |
|
12V |
| Ordering code IM-DB 9 |
|
127526 |