| Type |
|
Power side |
tel.side |
TV side |
| Elecrtical characteristics |
|
|
|
|
|
| Nominal operating voltage |
Un |
230VAC/50Hz |
110VDC |
50VDC |
| Max.continuous operating voltage |
Uc |
250VAC/50Hz |
170VDC |
70VDC |
| Nominal discharge current (8/20μs) |
In |
/ |
2.5kA |
5kA |
| Open circuit voltage of the combination wave generator |
Uoc |
3kV |
/ |
/ |
| Voltage protection level at In |
Up |
<1000V (L-N) |
700V |
700V |
| Respons time of overvoltage protection |
tA |
<25ns (L-N) |
<100ns |
<100ns |
| Limit frequency |
fG |
/ |
30MHz |
860MHz |
| Back-up fuse |
|
16A gL needed if not present in the network |
/ |
/ |
| Mechanical characteristics |
|
|
|
|
|
| Connection |
|
DIN 49 440-CE(7) III |
Input/Output: RJ11 |
IEC connector |
|
|
DIN 49 441-CEE(7) IV |
socket |
|
|
|
|
Grounding contact |
|
|
|
| Temperature range |
|
|
-40˚C…+80˚C |
|
|
| Degree of protection IEC/EN 60529 |
|
|
IP20 |
|
|
| Housing material |
|
|
Thermoplastic ; grey . extinguishing degree V-0 |
|
|
| Indication of disconnector operation |
|
|
green light |
|
|
| Ordering information |
|
|
|
|
| Ordering code ZES-76 TEL-TV |
|
|
121368 |
|
|